JC3R-125残留電流検出器

Electromagnetic TypeEarth leakage protectionBreaking capacity 6KA,or 10KARated current up to 125AAvailable in Type A or Type ACTripping sensitivity: 30mA, 100mA, 300mAConnection from top or bottomComplies with IEC61008-1, EN61008-1

Introduction

JC3R-125 4 pole RCDs may be used to provide earth fault protection on 3 phase, 3 wire systems, as the current balance mechanism does not require a neutral to be connected in order to operate effectively.
JC3R-125 RCDs must never be used as the sole method of direct contact protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur.
However W9 GROUP JC3R-125 4 pole RCDs do, ideally, require a neutral conductor to be provided on the supply side of the RCD in order to ensure that the test circuit operates satisfactorily. Where connection of a neutral supply is not possible, then an alternative method of ensuring that the test button is operational is to fit a suitably rated resistor between the load side neutral pole and a phase pole not associated with the normal test button operation.
JC3R-125 4 pole RCD is available in ac type and A type. AC type RCDs are only sensitive to sinusoidal type fault currents. A type RCDs, on the other hand, are sensitive to both sinusoidal currents and “unidirectional pulsed” currents, which may be present, for example, in systems with electronic devices for rectifying the current. These devices are capable of generating pulsed shape fault currents with continuous components that an AC type RCD is unable to recognize
JC3R-125 RCD provides protection against earth faults occurring in equipment and reduces the effects of electric shock on human beings and thus saves lives.
JC3R-125 RCD measures the current flowing in the live and neutral cables and if there is an imbalance, that is current flowing to earth above the RCD sensitivity, the RCD will trip and cut off the supply.
JC3R-125 RCDs incorporate a filtering device to provide protection against transient surges in the supply to the unit, thus reducing the occurrence of unwanted tripping

Information

スタンダード IEC61008-1, EN61008-1
Electronic features 定格電流(A) 25, 40, 50, 63, 80, 100, 125
タイプ Electromagnetic
Type(wave form of the leakage sensed) AC, A, AC-G, A-G AC-S and A-S are available
ポーランド人 3P+N
定格電圧 Ue(V) 3P+N: 400/415
評価感度 IΔn 30mA, 100mA, 300mA are available
絶縁電圧 Ui(V) 500
Rated residual making and breaking capacity IΔm 500(In=25/40A), 630(In=63A), 1000(In=80/100A)
定格周波数 50/60Hz
定格断面積 6KA, 10KA
定格インパルス耐圧(1.2/50)Uimp(V) 6,000
インダクタンス試験電圧(1分間、KV) 2.5
汚染度 2
機械的特徴 電気寿命 2,000
機械的寿命 4,000
接触位置インジケーター はい
保護レベル IP20
サーマルエレメントの設定時の基準温度(℃) 30
周囲温度(1日の平均が35℃以下) -5…+40
保管温度(℃) -25…+70
インストール ターミナル接続タイプ ケーブル/U型バスバー/ピン型バスバー
ケーブル用の端末サイズの上部/下部 25mm2/18-3AWG
バスバー用端子サイズの上部/下部 10mm2/18-8AWG
締めトルク 2.5N*m/22インチ-lbs
取り付け DINレール用 EN 60715(35mm)
接続 上部または下部から利用可能です