機能
電磁式タイプ
Earth Leakage Protection
Breaking capacity 6KA,10KA
Rated current up to 100A
Detect smooth DC 6mA residual currents
Tripping sensitivity: 30mA
Connection from top or bottom
Complies with IEC61008-1, IEC62955
申請
JC3RH-EV is a residual current circuit breaker that detects both AC and smooth DC fault currents, providing protection against the “blinding” effect of a smooth DC current on a standard Type A RCD. It’s specifically designed for individual EV chargers and trips if a smooth DC residual current exceeds 6mA, as it integrated a Residual Direct Current Detecting Device
Information
| スタンダード | IEC61009-1, IEC62955 | |
| 電気機能 | タイプ(地球の漏れを検知した波の形式) | EV(A+DC leakage current) |
| 定格電流(A) | 40, 63 | |
| ポーランド人 | 1P+N, 3P+N | |
| 定格電圧 Ue(V) | 1P+N: 230/240 3P+N: 400/415 | |
| 評価感度 IΔn | 0.03mA | |
| DC tripping threshold IΔdc | 6mA | |
| 絶縁電圧 Ui(V) | 500 | |
| Rated residual making and breaking capacity IΔm | 500(In=25A/40A), 630(In=63A) | |
| 定格周波数 | 50Hz | |
| 定格断面積 | 10KA | |
| SCPD fuse | 10000A | |
| Break time under IΔn | ≤0.1s | |
| 定格インパルス耐圧(1.2/50)Uimp(V) | 4,000 | |
| インダクタンス試験電圧(1分間、KV) | 2.5 | |
| 汚染度 | 2 | |
| 機械的特徴 | 電気寿命 | 2,000 |
| 機械的寿命 | 4,000 | |
| 接触位置インジケーター | はい | |
| 保護レベル | IP20 | |
| サーマルエレメントの設定時の基準温度(℃) | 30 | |
| 周囲温度(1日の平均が35℃以下) | -5…+40 | |
| 保管温度(℃) | -25…+70 | |
| インストール | ターミナル接続タイプ | ケーブル/U型バスバー/ピン型バスバー |
| ケーブル用の端末サイズの上部/下部 | 25mm2/18-3AWG | |
| バスバー用端子サイズの上部/下部 | 10mm2/18-8AWG | |
| 締めトルク | 2.5N*m/22インチ-lbs | |
| 取り付け | DINレール用 EN 60715(35mm) | |
| 接続 | 上部または下部から利用可能です |