サーキット保護製品

ホーム製品サーキット保護製品RCCBJC3RH-EV Residual Current Device
  • JC3RH-EV残留電流デバイス ギャラリー画像1
  • JC3RH-EV Residual Current Device Gallery image 2
  • JC3RH-EV Residual Current Device Gallery image 3
  • JC3RH-EV残留電流デバイス ギャラリー画像1
  • JC3RH-EV Residual Current Device Gallery image 2
  • JC3RH-EV Residual Current Device Gallery image 3

JC3RH-EV残留電流検出器

Electromagnetic TypeEarth Leakage ProtectionBreaking capacity 6KA,10KARated current up to 100ADetect smooth DC 6mA residual currentsTripping sensitivity: 30mAConnection from top or bottomComplies with IEC61008-1, IEC62955

機能
電磁式タイプ
Earth Leakage Protection
Breaking capacity 6KA,10KA
Rated current up to 100A
Detect smooth DC 6mA residual currents
Tripping sensitivity: 30mA
Connection from top or bottom
Complies with IEC61008-1, IEC62955

申請
JC3RH-EV is a residual current circuit breaker that detects both AC and smooth DC fault currents, providing protection against the “blinding” effect of a smooth DC current on a standard Type A RCD. It’s specifically designed for individual EV chargers and trips if a smooth DC residual current exceeds 6mA, as it integrated a Residual Direct Current Detecting Device

Information

スタンダード IEC61009-1, IEC62955
電気機能 タイプ(地球の漏れを検知した波の形式) EV(A+DC leakage current)
定格電流(A) 40, 63
ポーランド人 1P+N, 3P+N
定格電圧 Ue(V) 1P+N: 230/240 3P+N: 400/415
評価感度 IΔn 0.03mA
DC tripping threshold IΔdc 6mA
絶縁電圧 Ui(V) 500
Rated residual making and breaking capacity IΔm 500(In=25A/40A), 630(In=63A)
定格周波数 50Hz
定格断面積 10KA
SCPD fuse 10000A
Break time under IΔn ≤0.1s
定格インパルス耐圧(1.2/50)Uimp(V) 4,000
インダクタンス試験電圧(1分間、KV) 2.5
汚染度 2
機械的特徴 電気寿命 2,000
機械的寿命 4,000
接触位置インジケーター はい
保護レベル IP20
サーマルエレメントの設定時の基準温度(℃) 30
周囲温度(1日の平均が35℃以下) -5…+40
保管温度(℃) -25…+70
インストール ターミナル接続タイプ ケーブル/U型バスバー/ピン型バスバー
ケーブル用の端末サイズの上部/下部 25mm2/18-3AWG
バスバー用端子サイズの上部/下部 10mm2/18-8AWG
締めトルク 2.5N*m/22インチ-lbs
取り付け DINレール用 EN 60715(35mm)
接続 上部または下部から利用可能です