기능
전자기 타입
Earth Leakage Protection
Breaking capacity 6KA,10KA
Rated current up to 100A
Detect smooth DC 6mA residual currents
Tripping sensitivity: 30mA
Connection from top or bottom
Complies with IEC61008-1, IEC62955
응용
JC3RH-EV is a residual current circuit breaker that detects both AC and smooth DC fault currents, providing protection against the “blinding” effect of a smooth DC current on a standard Type A RCD. It’s specifically designed for individual EV chargers and trips if a smooth DC residual current exceeds 6mA, as it integrated a Residual Direct Current Detecting Device
Information
| 표준 | IEC61009-1, IEC62955 | |
| 전기 기능 | 형태(지하 배수관 누설 감지된 파형) | EV(A+DC leakage current) |
| 정격 전류(A) | 40, 63 | |
| 폴란드인 | 1P+N, 3P+N | |
| 정격 전압 Ue(V) | 1P+N: 230/240 3P+N: 400/415 | |
| 등급 감도 IΔn | 0.03mA | |
| DC tripping threshold IΔdc | 6mA | |
| 절연 전압 Ui(V) | 500 | |
| Rated residual making and breaking capacity IΔm | 500(In=25A/40A), 630(In=63A) | |
| 정격 주파수 | 50Hz | |
| 최대 절단 용량 | 10KA | |
| SCPD fuse | 10000A | |
| Break time under IΔn | ≤0.1s | |
| 인덕션 전류 저항 전압(1.2/50) Uimp(V) | 4,000 | |
| 1분 동안 인덕턴스 주파수에서 발생한 전압 (KV) | 2.5 | |
| 오염 정도 | 2 | |
| 기계적 특징 | 전기 수명 | 2,000 |
| 기계적 수명 | 4,000 | |
| 접촉 위치 표시기 | 네 | |
| 보호 수준 | IP20 | |
| 열체 열 설정 기준 온도(℃) | 30 | |
| 기온(일일 평균 ≤35℃) | -5…+40 | |
| 저장 온도(℃) | -25…+70 | |
| 설치 | 터미널 연결 유형 | 케이블/U형 버스바/핀형 버스바 |
| 케이블의 상단/하단 터미널 사이즈 | 25mm2/18-3AWG | |
| 버스바용 터미널 사이즈 상단/하단 | 10mm2/18-8AWG | |
| 강력한 토크 | 2.5N*m/22인치-파운드 | |
| 장착 | DIN 레일 EN 60715(35mm)에 맞게 | |
| 연결 | 상단 또는 하단에서 사용할 수 있습니다. |