جایگزین کننده جریان انباشته JC3R-125

Electromagnetic TypeEarth leakage protectionBreaking capacity 6KA,or 10KARated current up to 125AAvailable in Type A or Type ACTripping sensitivity: 30mA, 100mA, 300mAConnection from top or bottomComplies with IEC61008-1, EN61008-1

Introduction

JC3R-125 4 pole RCDs may be used to provide earth fault protection on 3 phase, 3 wire systems, as the current balance mechanism does not require a neutral to be connected in order to operate effectively.
JC3R-125 RCDs must never be used as the sole method of direct contact protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur.
However W9 GROUP JC3R-125 4 pole RCDs do, ideally, require a neutral conductor to be provided on the supply side of the RCD in order to ensure that the test circuit operates satisfactorily. Where connection of a neutral supply is not possible, then an alternative method of ensuring that the test button is operational is to fit a suitably rated resistor between the load side neutral pole and a phase pole not associated with the normal test button operation.
JC3R-125 4 pole RCD is available in ac type and A type. AC type RCDs are only sensitive to sinusoidal type fault currents. A type RCDs, on the other hand, are sensitive to both sinusoidal currents and “unidirectional pulsed” currents, which may be present, for example, in systems with electronic devices for rectifying the current. These devices are capable of generating pulsed shape fault currents with continuous components that an AC type RCD is unable to recognize
JC3R-125 RCD provides protection against earth faults occurring in equipment and reduces the effects of electric shock on human beings and thus saves lives.
JC3R-125 RCD measures the current flowing in the live and neutral cables and if there is an imbalance, that is current flowing to earth above the RCD sensitivity, the RCD will trip and cut off the supply.
JC3R-125 RCDs incorporate a filtering device to provide protection against transient surges in the supply to the unit, thus reducing the occurrence of unwanted tripping

Information

استاندارد IEC61008-1, EN61008-1
Electronic features مقاومت جریان ورودی (A) 25, 40, 50, 63, 80, 100, 125
نوع Electromagnetic
Type(wave form of the leakage sensed) AC, A, AC-G, A-G AC-S and A-S are available
پوشندگان لهستانی 3P+N
ولتاژ رتبه‌دهی شده Ue (V) 3P+N: 400/415
حساسیت رتبه‌دهی شده IΔn 30mA, 100mA, 300mA are available
ولتاژ عایق بندی Ui (V) 500
Rated residual making and breaking capacity IΔm 500(In=25/40A), 630(In=63A), 1000(In=80/100A)
فراوانی رتبهبندی شده ۵۰/۶۰ هرتز
قدرت شکسته شدن بر اساس رتبه بندی 6KA, 10KA
تولید برق ناپایدار (1.2/50) Uimp (V) 6,000
تنظیم ولتاژ تست دی الکتریک در فرکانس داخلی برای ۱ دقیقه (کیلوولت) 2.5
سطح آلودگی 2
ویژگی‌های مکانیکی زندگی الکتریکی 2,000
زمان کارکرد مکانیکی 4,000
نمایشگر موقعیت تماس بله
سطح حفاظت IP20
دمای مرجع برای تنظیم عنصر حرارتی (درجه سانتیگراد) 30
استاندارد دمای محیط (با میانگین روزانه ≤35 ℃) -5…+40
دمای ذخیره سازی (درجه سانتیگراد) -25…+70
ارائه نصب نوع اتصال ترمینال کابل/پیوستهای U-type/پیوستهای Pin-type
ابعاد بالایی/پایینی ترمینال برای کابل 25 میلی متر مربع / 18-3AWG
ابعاد پایانه بالایی/پایینی برای Busbar 10 میلی متر مربع / 18-8AWG
تنگ کردن گشتاور 2.5N*m/22In-lbs
قرارگیری بر روی ریل DIN EN 60715 (35 میلی متر)
اتصال از بالا یا پایین قابل استفاده هستند