Introduction
JC3R-125 4 pole RCDs may be used to provide earth fault protection on 3 phase, 3 wire systems, as the current balance mechanism does not require a neutral to be connected in order to operate effectively.
JC3R-125 RCDs must never be used as the sole method of direct contact protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur.
However W9 GROUP JC3R-125 4 pole RCDs do, ideally, require a neutral conductor to be provided on the supply side of the RCD in order to ensure that the test circuit operates satisfactorily. Where connection of a neutral supply is not possible, then an alternative method of ensuring that the test button is operational is to fit a suitably rated resistor between the load side neutral pole and a phase pole not associated with the normal test button operation.
JC3R-125 4 pole RCD is available in ac type and A type. AC type RCDs are only sensitive to sinusoidal type fault currents. A type RCDs, on the other hand, are sensitive to both sinusoidal currents and “unidirectional pulsed” currents, which may be present, for example, in systems with electronic devices for rectifying the current. These devices are capable of generating pulsed shape fault currents with continuous components that an AC type RCD is unable to recognize
JC3R-125 RCD provides protection against earth faults occurring in equipment and reduces the effects of electric shock on human beings and thus saves lives.
JC3R-125 RCD measures the current flowing in the live and neutral cables and if there is an imbalance, that is current flowing to earth above the RCD sensitivity, the RCD will trip and cut off the supply.
JC3R-125 RCDs incorporate a filtering device to provide protection against transient surges in the supply to the unit, thus reducing the occurrence of unwanted tripping
Information
| 표준 | IEC61008-1, EN61008-1 | |
| Electronic features | 정격 전류(A) | 25, 40, 50, 63, 80, 100, 125 |
| 형태 | Electromagnetic | |
| Type(wave form of the leakage sensed) | AC, A, AC-G, A-G AC-S and A-S are available | |
| 폴란드인 | 3P+N | |
| 정격 전압 Ue(V) | 3P+N: 400/415 | |
| 등급 감도 IΔn | 30mA, 100mA, 300mA are available | |
| 절연 전압 Ui(V) | 500 | |
| Rated residual making and breaking capacity IΔm | 500(In=25/40A), 630(In=63A), 1000(In=80/100A) | |
| 정격 주파수 | 50/60Hz | |
| 최대 절단 용량 | 6KA, 10KA | |
| 인덕션 전류 저항 전압(1.2/50) Uimp(V) | 6,000 | |
| 1분 동안 인덕턴스 주파수에서 발생한 전압 (KV) | 2.5 | |
| 오염 정도 | 2 | |
| 기계적 특징 | 전기 수명 | 2,000 |
| 기계적 수명 | 4,000 | |
| 접촉 위치 표시기 | 네 | |
| 보호 수준 | IP20 | |
| 열체 열 설정 기준 온도(℃) | 30 | |
| 기온(일일 평균 ≤35℃) | -5…+40 | |
| 저장 온도(℃) | -25…+70 | |
| 설치 | 터미널 연결 유형 | 케이블/U형 버스바/핀형 버스바 |
| 케이블의 상단/하단 터미널 사이즈 | 25mm2/18-3AWG | |
| 버스바용 터미널 사이즈 상단/하단 | 10mm2/18-8AWG | |
| 강력한 토크 | 2.5N*m/22인치-파운드 | |
| 장착 | DIN 레일 EN 60715(35mm)에 맞게 | |
| 연결 | 상단 또는 하단에서 사용할 수 있습니다. |