홈제품회로 보호 제품RCCBJC3R-125 Residual Current Device
  • JC3R-125 잔류 전류 장치 갤러리 이미지 1
  • JC3R-125 Residual Current Device Gallery image 2
  • JC3R-125 Residual Current Device Gallery image 3
  • JC3R-125 잔류 전류 장치 갤러리 이미지 1
  • JC3R-125 Residual Current Device Gallery image 2
  • JC3R-125 Residual Current Device Gallery image 3

JC3R-125 잔류 전류 장치

Electromagnetic TypeEarth leakage protectionBreaking capacity 6KA,or 10KARated current up to 125AAvailable in Type A or Type ACTripping sensitivity: 30mA, 100mA, 300mAConnection from top or bottomComplies with IEC61008-1, EN61008-1

Introduction

JC3R-125 4 pole RCDs may be used to provide earth fault protection on 3 phase, 3 wire systems, as the current balance mechanism does not require a neutral to be connected in order to operate effectively.
JC3R-125 RCDs must never be used as the sole method of direct contact protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur.
However W9 GROUP JC3R-125 4 pole RCDs do, ideally, require a neutral conductor to be provided on the supply side of the RCD in order to ensure that the test circuit operates satisfactorily. Where connection of a neutral supply is not possible, then an alternative method of ensuring that the test button is operational is to fit a suitably rated resistor between the load side neutral pole and a phase pole not associated with the normal test button operation.
JC3R-125 4 pole RCD is available in ac type and A type. AC type RCDs are only sensitive to sinusoidal type fault currents. A type RCDs, on the other hand, are sensitive to both sinusoidal currents and “unidirectional pulsed” currents, which may be present, for example, in systems with electronic devices for rectifying the current. These devices are capable of generating pulsed shape fault currents with continuous components that an AC type RCD is unable to recognize
JC3R-125 RCD provides protection against earth faults occurring in equipment and reduces the effects of electric shock on human beings and thus saves lives.
JC3R-125 RCD measures the current flowing in the live and neutral cables and if there is an imbalance, that is current flowing to earth above the RCD sensitivity, the RCD will trip and cut off the supply.
JC3R-125 RCDs incorporate a filtering device to provide protection against transient surges in the supply to the unit, thus reducing the occurrence of unwanted tripping

Information

표준 IEC61008-1, EN61008-1
Electronic features 정격 전류(A) 25, 40, 50, 63, 80, 100, 125
형태 Electromagnetic
Type(wave form of the leakage sensed) AC, A, AC-G, A-G AC-S and A-S are available
폴란드인 3P+N
정격 전압 Ue(V) 3P+N: 400/415
등급 감도 IΔn 30mA, 100mA, 300mA are available
절연 전압 Ui(V) 500
Rated residual making and breaking capacity IΔm 500(In=25/40A), 630(In=63A), 1000(In=80/100A)
정격 주파수 50/60Hz
최대 절단 용량 6KA, 10KA
인덕션 전류 저항 전압(1.2/50) Uimp(V) 6,000
1분 동안 인덕턴스 주파수에서 발생한 전압 (KV) 2.5
오염 정도 2
기계적 특징 전기 수명 2,000
기계적 수명 4,000
접촉 위치 표시기 네
보호 수준 IP20
열체 열 설정 기준 온도(℃) 30
기온(일일 평균 ≤35℃) -5…+40
저장 온도(℃) -25…+70
설치 터미널 연결 유형 케이블/U형 버스바/핀형 버스바
케이블의 상단/하단 터미널 사이즈 25mm2/18-3AWG
버스바용 터미널 사이즈 상단/하단 10mm2/18-8AWG
강력한 토크 2.5N*m/22인치-파운드
장착 DIN 레일 EN 60715(35mm)에 맞게
연결 상단 또는 하단에서 사용할 수 있습니다.