MCCB circuit breaker Residual Current JC3RH-BS Type B

機能
● Electromagnetic Type
● Earth leakage protection
● Breaking capacity 6kA,10kA
● Rated current up to 100A
● Detect smooth DC residual currents
● Tripping sensitivity: 30mA,100mA,300mA
● Connection from top or bottom
● Complies with IEC 61008-1 & IEC62423
申請
JC3RH-BS Type B RCCBs are suitable for non-linear circuits that are able to generate leakages with high direct current (higher than 6 mA) and/or high frequency components, for example single-phase or poly-phase rectifiers, rectifiers with active correction of the power factor, continuous voltage generator with no separation from AC networks and inverters at variable frequency.
B Type
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.


| スタンダード | IEC62423 & IEC61008-1 | |
|
Electrical features |
Type (wave form of the earth leakage sensed) | B |
| 定格電流 In | 25A, 40A, 63A, 80A, 100A | |
| ポーランド人 | 1P+N, 3P+N | |
| Rated voltage Ue | 1P+N:230V/240V~; 3P+N:400V/415V~; | |
| Rated sensitivity I∆n | 0.03A, 0.1A, 0.3A | |
| 絶縁電圧 Ui | 500V | |
| Rated residual making and breaking capacity I∆m | 500 (In=25A/40A), 630 (In=63A), 1000(In=80A/100A | |
| Short-circuit current Inc=I∆c | 6kA,10kA | |
| SCPD fuse | 10000A | |
| break time under I∆n | ≤0.1 S | |
| 定格周波数 | 50Hz | |
| Rated impulse withstand voltage(1.2/50) Uimp | 4,000V | |
| Dielectric test voltage at ind. Freq. for 1 min | 2.5 kV | |
| 汚染度 | 2 | |
|
Mechanical features |
電気寿命 | 2, 000 |
| 機械的寿命 | 10,000 | |
| Fault current indicator | はい | |
| 保護レベル | IP20 | |
| Ambient temperature (with daily average≤35°C) | -25°C…+40°C | |
| Storage temperation | -25°C…+70°C | |
| インストール | ターミナル接続タイプ | ケーブル/U型バスバー/ピン型バスバー |
| ケーブル用の端末サイズの上部/下部 | 25/35 mm² | |
| 18-3/18-2 AWG | ||
| Terminal size top/bottom for busbar | 10/16 mm² | |
| 18-8/18-5 AWG | ||
| 締めトルク | 2.5 N·m | |
| 22 In-Ibs. | ||
| 取り付け | On DIN rail EN 60715 (35mm) | |
| 接続 | From top and bottom |