サーキット保護製品

  • JCMS100 100A Main Switch Isolator Gallery image 1
  • JCMS100 100A Main Switch Isolator Gallery image 2
  • JCMS100 100A Main Switch Isolator Gallery image 3
  • JCMS100 100A Main Switch Isolator Gallery image 1
  • JCMS100 100A Main Switch Isolator Gallery image 2
  • JCMS100 100A Main Switch Isolator Gallery image 3

JCMS100 100A Main Switch Isolator

Built-in plastic lock kitWith contact indicatorRated current up to 100A1 Pole, 2 Pole, 3 Pole, 4 Pole are availableComply with IEC60947-3

Product Detail

Main feature
Built-in plastic lock kit
With contact indicator
Rated current up to 100A
1 Pole, 2 Pole, 3 Pole, 4 Pole are available
Comply with IEC60947-3

スタンダード  IEC/EN 60947-3

電気機能

定格電流(A) 32,40,50,63,80,100,125
ポーランド人 1P,  2P, 3P, 4P
Rated voltage Ue(V) 230/400~240/415
絶縁電圧 Ui(V) 500
定格周波数 50/60Hz
Rated impulse withstand voltage(1.2/50) Uimp (V) 4,000
Rated short-time withstand current lcw 12le, 1s
Rated making and breaking capacity 3le, 1.05Ue, cosφ=0.65
Rated short circuit making capacity 20le, t=0.1s
Dielectric test voltage at ind. Freq. for 5s 2kV
汚染度 2
Uilization category AC-22A

機械的特徴

電気寿命 1500
機械的寿命 8500
接触位置インジケーター はい
保護レベル IP20
Ambient temperature (with daily average ≤35℃) -5…+40
Storage temperation (℃) -25…+70
インストール ターミナル接続タイプ ケーブル/U型バスバー/ピン型バスバー
ケーブル用の端末サイズの上部/下部

50mm2  / 18-1/0 AWG

バスバー用端子サイズの上部/下部

35mm2  / 18-2 AWG

締めトルク

2.5 N*m  /  22 In-Ibs.

取り付け On DIN rail EN 60715 (35mm) by means of fast clip device
接続 From top and bottom