HomeBlogRCD Types AC, A and B vs MCB Trip Curves

RCD Types AC, A and B vs MCB Trip Curves

Release Time: 2026-01-15

An electrical schedule that says only “Type B breaker” is ambiguous. It may mean an RCD with Type B residual-current detection, or an MCB with a B overcurrent curve. Those are different functions, and confusing them can leave an electronic load with the wrong protection.

The direct answer is that AC, A and B usually describe residual-current waveform capability in an RCD specification. B, C and D describe magnetic overcurrent characteristics in an MCB specification. An RCBO combines functions, so its order can require both a residual-current type and an overcurrent curve. Specify each field separately.

Residual-current types describe the leakage waveform

A residual-current device compares current leaving and returning through its sensing arrangement. Type AC addresses sinusoidal alternating residual current. Type A additionally addresses pulsating DC residual current within its declared test scope. Type B covers additional waveforms including smooth DC within its declared scope; it is not simply a higher-current version of Type A.

The load matters. Rectifiers, variable-speed equipment and charging systems can introduce waveforms that a simple AC assumption misses. Obtain the equipment manufacturer’s protective-device instructions and follow installation rules for the destination market. A general claim that all electronic equipment requires Type B is just as unhelpful as assuming Type AC is always adequate.

Marking What it describes What it does not establish
Type AC Sinusoidal AC residual-current response Overcurrent curve or DC suitability
Type A AC and pulsating DC residual-current response Full smooth-DC detection
Type B RCD Additional waveforms including smooth DC within scope A B-curve MCB characteristic

Review the difference between RCBO and RCCB protection before allocating overload and residual-current functions.

MCB curves describe overcurrent operation

An MCB’s magnetic trip curve concerns high-current pickup, whereas its thermal element responds to sustained overload. The familiar B, C and D labels therefore answer a different question from Type AC, A or B on an RCD. Select the curve using load inrush, conductor protection and the available fault current needed to achieve disconnection.

Do not choose a curve with a higher magnetic threshold simply to conceal repeated trips. Investigate overload, starting conditions and faults. For low fault-current circuits, a higher threshold can affect the time required to disconnect a fault. Use the exact manufacturer’s time-current curves and the installation calculation.

The guide to residual-current protection describes the installation conditions that a device label alone cannot establish.

JC3RH-B左侧面2P.png

Specifying an RCBO without ambiguity

Write the current rating, poles, voltage, residual-current type, residual-current sensitivity, overcurrent curve and short-circuit rating as separate entries. For example, “Type A, curve B” is a coherent description because the two labels refer to different functions. It is not a Type B RCD specification.

Project question Required information
What current can the circuit carry? Design load, conductor ampacity and device current rating
Which leakage waveform can occur? Equipment data and residual-current type
Will inrush cause unwanted operation? Overcurrent curve and starting envelope
Can the device interrupt the fault? Short-circuit rating at circuit voltage
Is additional protection required? Sensitivity and applicable installation rules

Before replacing a device, check neutral routing and the complete circuit arrangement. A shared neutral can create residual-current operation that changing the curve cannot solve. Isolate and investigate through a competent person rather than treating a new label as a cure.

Standards and procurement evidence

IEC 61008-1 covers RCCBs without integral overcurrent protection; IEC 61009-1 covers RCBOs. IEC 60898-1 is a separate reference for AC household and similar overcurrent circuit-breakers. The IET’s RCD-type guidance explains why waveform selection follows the connected equipment. A catalogue standard reference does not itself certify a particular model.

Ask W9 Group for the exact device type, order code and supporting technical documents. Keep the waveform selection, curve and installation verification in the circuit schedule so a later replacement does not silently change the protection boundary.

Frequently asked questions

Is a Type B RCD the same as a B-curve MCB?

No. Type B RCD describes residual-current waveform detection, while a B curve describes magnetic overcurrent pickup. An installation may need both functions in separate devices or an appropriately specified RCBO.

Can Type A detect every DC leakage current?

No. Type A covers defined AC and pulsating DC residual currents, not unrestricted smooth DC. Check the load instructions and applicable rules for additional detection or a different RCD type.

Is Type AC suitable for every household circuit?

No. Connected equipment and local installation requirements can require another type. Select from the expected residual-current waveform, not the building label alone.

Will changing from a B curve to a C curve fix RCD trips?

It does not change residual-current waveform detection or sensitivity. Diagnose whether the trip is caused by overcurrent, leakage or wiring before altering the protective arrangement.

References

For waveform and pole selection, contact W9 Group with the circuit topology, load equipment and destination-market rules.