Circuit Protection Products

HomeProductsCircuit Protection ProductsRCCBMCCB circuit breaker Residual Current JC3RH-BS Type B
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 1
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 2
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 3
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 1
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 2
  • MCCB circuit breaker Residual Current JC3RH-BS Type B Gallery image 3

MCCB circuit breaker Residual Current JC3RH-BS Type B

JC3RH-BS Type B RCCBs are suitable for non-linear circuits that are able to generate leakages with high direct current (higher than 6 mA) and/or high frequency components, for example single-phase or poly-phase rectifiers, rectifiers with active correction of the power factor, continuous voltage generator with no separation from AC networks and inverters at variable frequency.

MCCB circuit breaker Residual Current JC3RH-BS Type B detail image 1

Features

● Electromagnetic Type

● Earth leakage protection

● Breaking capacity 6kA,10kA

● Rated current up to 100A

● Detect smooth DC residual currents

● Tripping sensitivity: 30mA,100mA,300mA

● Connection from top or bottom

● Complies with IEC 61008-1 & IEC62423

Application

JC3RH-BS Type B RCCBs are suitable for non-linear circuits that are able to generate leakages with high direct current (higher than 6 mA) and/or high frequency components, for example single-phase or poly-phase rectifiers, rectifiers with active correction of the power factor, continuous voltage generator with no separation from AC networks and inverters at variable frequency.

B Type

Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

MCCB circuit breaker Residual Current JC3RH-BS Type B detail image 2

MCCB circuit breaker Residual Current JC3RH-BS Type B detail image 3

Standard IEC62423 & IEC61008-1
Electrical
features
Type (wave form of the earth leakage sensed) B
Rated current In 25A, 40A, 63A, 80A, 100A
Poles 1P+N, 3P+N
Rated voltage Ue 1P+N:230V/240V~; 3P+N:400V/415V~;
Rated sensitivity I∆n 0.03A, 0.1A, 0.3A
Insulation voltage Ui 500V
Rated residual making and breaking capacity I∆m 500 (In=25A/40A), 630 (In=63A), 1000(In=80A/100A
Short-circuit current Inc=I∆c 6kA,10kA
SCPD fuse 10000A
break time under I∆n ≤0.1 S
Rated frequency 50Hz
Rated impulse withstand voltage(1.2/50) Uimp 4,000V
Dielectric test voltage at ind. Freq. for 1 min 2.5 kV
Pollution degree 2
Mechanical
features
Electrical life 2, 000
Mechanical life 10,000
Fault current indicator Yes
Protection degree IP20
Ambient temperature (with daily average≤35°C) -25°C…+40°C
Storage temperation -25°C…+70°C
Installation Terminal connection type Cable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cable 25/35 mm²
18-3/18-2 AWG
Terminal size top/bottom for busbar 10/16 mm²
18-8/18-5 AWG
Tightening torque 2.5 N·m
22 In-Ibs.
Mounting On DIN rail EN 60715 (35mm)
Connection From top and bottom

MCCB circuit breaker Residual Current JC3RH-BS Type B detail image 4