JC3LE-2P RCBO: 6 kA Ratings and Circuit Selection

Release Time: 2026-01-01

A two-pole RCBO order can look complete while omitting the residual-current waveform and fault duty. For JC3LE-2P, those details matter more than a broad promise to prevent shocks or fires: the protective functions must match the circuit and its installation rules.

Summary: The JC3LE-2P is an RCBO: it combines overcurrent protection and 残留電流保護 in one two-pole device. Published product information describes 6-63 A choices, B or C curves, a Type A residual-current option in the current technical table and a 6 kA short-circuit rating; verify the exact order code before relying on any value. Start with circuit current, waveform, sensitivity, poles, fault level and local installation rules, then document the test-button and commissioning checks.

JC3LE-2P Protection Scope

An RCBO is selected by the protection boundary it must cover, not by the label alone. The MCB element addresses overload and short circuit; the residual-current element compares current paths and trips when the declared residual current is exceeded.

JC3LE-2P Protection Functions

The published JC3LE-2P description identifies double-pole switching, a contact indicator and selectable B/C curves. The ordered 残留電流型 must be matched to the connected load and the local code. A 30 mA, 100 mA or 300 mA sensitivity is a project decision; do not infer shock or fire protection from a generic RCBO name.

Installation boundary

Route the neutral through the sensing path specified by the wiring diagram, torque terminals to the current instructions, and verify line/load orientation. Test the device with the required instrument and record the result; a front test button does not replace the complete commissioning procedure.

The 4極RCBOガイド アラーム信号、負荷電流、および 破壊能力 別途確認が必要です。.

RCBO Specification Checks

決定次元 確認すべきこと なぜ重要なのか
Overcurrent Rated current and B/C curve Matches conductor ampacity and inrush
残留電流 Type AC or Type A; IΔn Matches waveform and protection objective
故障時の義務 Declared breaking capacity Must exceed prospective fault current
Switching Two-pole neutral isolation Supports the specified isolation method

Reading the current JC3LE-2P listing

The current W9 product table lists 6 kA at 230/240 V, 50/60 Hz, 6–63 A options, 30/100/300 mA sensitivity and B or C overcurrent curves. Its waveform table identifies Type A. These are separate specification fields: a 6 kA short-circuit rating does not describe residual-current sensitivity, and a B curve does not make the device a Type B RCD.

An order should identify all these fields together. For example, a circuit requiring additional protection cannot adopt a higher residual-current threshold simply to stop unwanted operation. Investigate standing leakage, shared neutrals and connected equipment, then apply the destination rules and manufacturer instructions. Do not use this article as a live-work procedure.

比較の仕方 RCBOおよびRCCBの保護 インテグレート型過電流保護と残留電流検出を区別するのに役立ちます。.

RCBO Application Requirements

申請 Check before release
Lighting and socket circuits Load current, curve and 30 mA requirement
Motor or refrigeration branch Starting current and nuisance-trip margin
電子機器用負荷 Residual-current waveform and Type A need

基準とコンプライアンス

IEC 61009-1 is the product standard for RCBOs; IEC 61008-1 covers RCCBs without integral overcurrent protection. IEC 60364-4-41 addresses protection against electric shock at installation level. A standard reference is not a certificate for every model, so request the exact declaration, test scope and wiring diagram for the supplied device.

選定および試運転チェックリスト

  1. 記録電圧、電流、ポール数、負荷プロファイル、および将来的な故障電流。.
  2. 承認された図面と標準仕様に、正確なモデルと付属品を一致させます。.
  3. レビューの調整、許可の取得、温度および保管環境の確認を行う。.
  4. 範囲内で宣言書、試験資料、および設置手順書の提出を求めます。.
  5. 導入時の記録設定、トルク値、機能テスト結果を記録します。.

よくある質問

Is JC3LE-2P a 10 kA RCBO?

The current product table lists 6 kA, not 10 kA. Use the delivered order code and marking to confirm the rating at the actual circuit voltage; do not borrow a rating from a different JC3LE model.

Does the B curve mean Type B residual-current protection?

No. B and C curves describe overcurrent operation, while Type A describes residual-current waveform capability. Both fields must be specified independently.

Can a 300 mA option replace a required 30 mA device?

Not merely to avoid tripping. Sensitivity must satisfy the circuit’s protection objective and local installation rules; a higher threshold is not an equivalent substitute for required additional protection.

Why does an RCBO trip with its load disconnected?

A shared or incorrectly routed neutral, wiring defect or device problem may remain even when the appliance is removed. A competent electrician should isolate and test the circuit rather than repeatedly reset it.

参考文献

Review the JC3LE-2P information with the current datasheet and contact W9 Group with the circuit schedule, fault level and destination-market requirements.

回路レベルでの選択については、, W9グループへのお問い合わせ 回路図、負荷波形、接地配置、および適用可能な設置規則を考慮して。.