MCCB circuit breaker WLM6E-630A-3300 3P/4P WLM6E SeriesMCCB electronic circuit breaker 400V/690V 630A 3 poles/4 poles lsig breaker
Основные характеристики MCCB
One of the key advantages of the WLM6E Electronic Type MCCB is its LSIG protection capability. LSIG protection refers to the combination of Long-Time, Short-Time, Instantaneous, and Ground Fault protection functions within a single device. This comprehensive protection scheme allows the MCCB to respond to a wide range of fault conditions, ensuring that the electrical system is effectively safeguarded against different types of faults.
The Long-Time protection function of the WLM6E MCCB is designed to handle overcurrent conditions that persist for an extended period. This feature is crucial for protecting electrical systems from sustained overloads, which can lead to overheating and damage to the conductors and equipment. By accurately detecting and responding to long-term overcurrents, the WLM6E MCCB helps prevent potential hazards and ensures the continuous and safe operation of the electrical system.
Основные показатели работы выключателя серии WLM6E
| Преобразователь цепи с корпусом в форме листка бумаги WLM6E | 630 | |||||||||||||
| Максимальный рабочий ток (в А), 40°C | 6 регулируемых кнопок | 400-440-460-480-500-530-560-600-630 | ||||||||||||
| 3 регулируемых рычага | 400-440-460-480-500-530-560-600-630 | |||||||||||||
| Электрические характеристики | ||||||||||||||
| Определенная изоляционная напряженность Ui (В) | 1000 | |||||||||||||
| Определенная импульсная прочность на напряжение (kV) | 8 | |||||||||||||
| Определенная рабочая напряженность Ue(V), переменный ток 50/60 Гц | 380/400/415,440,500,660/690 | |||||||||||||
| Код прорыва пропускной способности | C | S | M | H | Q | |||||||||
| Число столбов | 1P | – | – | – | – | – | ||||||||
| 2P | – | – | – | – | – | |||||||||
| 3P | – | – | ■ | ■ | ■ | |||||||||
| 4P | – | – | ■ | ■ | ■ | |||||||||
| Число столбов | AC220/230/240В | – | – | – | – | – | ||||||||
| AC380/400/415В | – | – | 70 | 100 | 150 | |||||||||
| AC440V | – | – | – | – | – | |||||||||
| AC500V | – | – | – | – | 65 | |||||||||
| AC660/690В | – | – | 8 | 8 | 20 | |||||||||
| Число столбов | AC220/230/240В | – | – | – | – | – | ||||||||
| AC380/400/415В | – | – | 50 | 70 | 150 | |||||||||
| AC440V | – | – | – | – | – | |||||||||
| AC500V | – | – | – | – | 65 | |||||||||
| AC660/690В | – | – | 8 | 8 | 20 | |||||||||
| Rated short-time withstand current Icw (kA,1s) | 10 | |||||||||||||
| Стандартный | ||||||||||||||
| Категория использования | B | |||||||||||||
| Температура окружающей среды | ||||||||||||||
| Безопасность изоляции | ■ | |||||||||||||
| Расстояние искрения | 0 | |||||||||||||
|
Механический срок службы (Ко второй переработке) |
Поддержание работоспособности | 15000 | ||||||||||||
|
Электрическая жизнь (Ко второй переработке) |
AC415V,In | 8000 | ||||||||||||
| AC690V,В | 1500 | |||||||||||||
| Выпускаемые единицы | ||||||||||||||
| Защита от распространения | E | ■ | ||||||||||||
| Защита двигателя | E | ■ | ||||||||||||
| Установка и подключение | ||||||||||||||
| Исправлено | Передний контакт | ■ | ||||||||||||
| Задний разъём | ■ | |||||||||||||
| Пластиковый адаптер | Передний контакт | ■ | ||||||||||||
| Задний разъём | ■ | |||||||||||||
| Развертывание | Передний контакт | – | ||||||||||||
| Задний разъём | – | |||||||||||||
| DIN-рейлинги | Передний контакт | ■ | ||||||||||||
| Размер | ||||||||||||||
|
Размер (мм) Ш×В×Г |
Ширина (3P/4P) | 140/184 | ||||||||||||
| Высота | 257 | |||||||||||||
| Глубина | 103/111 | |||||||||||||
| Масса | ||||||||||||||
| Защита от распространения | 1P | – | ||||||||||||
| 2P | – | |||||||||||||
| 3P | 5.391 | |||||||||||||
| 4P | 7.266 | |||||||||||||