محصولات صنعتی

خانهمحصولاتمحصولات صنعتیMCCBM6 SeriesWLM6ELYMCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 1
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 2
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 3
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 1
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 2
  • MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles Gallery image 3

MCCB circuit breaker WLM6ELY-400A-4300 3P WLM6E Series electronic circuit breaker lsig 400A 4 Poles

Rated Current : 400A Number Of Poles : 3P/4P Rated Working Voltage : 400V/690V

Residual Current Circuit Breaker with Liquid Crystal Display (RCCB with LCD Type): Functions and Benefits

Trip Status Display: When a fault occurs, the RCCB with LCD display provides a clear indication of the trip status, including the cause of the trip and the time of occurrence. This information is valuable for diagnosing the root cause of electrical issues and implementing corrective measures.
Historical Data Logging: RCCBs with LCD displays are capable of logging historical data related to electrical events and faults. This data can be used for analysis, trend monitoring, and compliance with regulatory requirements.

Main performance index of WLM6LEY series circuit breaker

WLM6LEY Moulded Case Circuit Breaker 400
Rated current (A) of circuit breaker 40℃ Fix type 250-315-350-400
Lcd type 250-315-350-400
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage (kV) 8
Rated operational voltage Ue(V),AC 50/60Hz AC400V
Breaking capacity code C S M H
Number of poles 2P – – – –
3P – – ■ ■
4P – – ■ ■
Rated ultimate
short-circuit breaking
capacity Icu (kA)
AC380/400/415V – – 50 65
AC380/400/415V – – 35 42
Rated residual making and breaking capacity
I△ m(kA)
AC220/230/240V – – – 16.5
Limit non-actuating time △ t (ms) 0.06s/0.2s/0.5s/1s
Leakage alarm non-tripping function □
overcurrent tripping type Themal type
Leakage tripping type Electronic Type
Residual current type AC
Standard IEC/EN 60947-2
Utilization category A
Ambient temperature -40℃ ~+70 ℃
Safety of insulation ■
Arcing distance 0
Mechanical life
(CO recycle)
Maintenance 15000
Electrical life
(CO recycle)
AC415V,In 8000
AC690V,In 2000
Release units
Mounting and connection
Fixed Front connection ■
Rear connection ■
Plug-in Front connection ■
Rear connection ■
Draw-out Front connection –
Rear connection –
DIN rail Front connection ■
Dimension
Dimension (mm)
W×H×D
Width (2P/3P/4P) -/140/184
Height 257
Depth 103
Weight
Distribution protection 2P –
3P 4.758
4P 6.314

Information of three-knob intelligent controller
1 Alarm LED indicator
2 Pre-alarm LED indicator
3 Operation LED indicator
4 Setting current of overload long-time delay current IR(A)
5 Setting current of short circuit short-time delay time Isd(A)
6 Current setting of short-circuit short delay time Ii(A)