بررسی مزایای پریزهای مدار لیسگ برای سیستمهای برق مدرن
LSIG functions give an engineer separate protection settings; they do not automatically make a system selective or safe at any setting. The benefit depends on the circuit study and the exact release supplied.
تعداد پیکر بندی MCCB should be shortlisted by the required وظایف حفاظتی and documented electrical duty.
راهنمای قطع مدارهای قالبدوزی اشاره میکند که اندازه فریم، رتبهبندی و رفتار در هنگام حرکت چگونه متفاوت هستند.




Test and govern the settings
| صحنه | شواهد برای حفظ |
|---|---|
| Study | Source assumptions and coordinated curves |
| اتصالدهی | Exact release, sensor and neutral arrangement |
| مقاله آزمایشی | Manufacturer-approved method and results |
| نقل اختیار | As-left settings and authorised revision |
| Change | Reassessment and updated test record |
IEC 60947-2 product declarations do not approve an arbitrary delay or sensing arrangement. Follow the release’s test instructions, recognising the different scope of primary and secondary injection. Include test equipment, engineering, spares and inspection in lifecycle cost. Ask W9 for exact LSIG release documents rather than a broad claim of advanced protection.
از این شرایط فنی برای MCCBs برای بررسی مشخصات با کد سفارش و فایل پروژه مطابقت دهید.





Assign each LSIG function a design job
Long-time pickup and delay protect the sustained-load region within the conductor limit. Short-time delay can support downstream discrimination but increases exposure while a fault persists. Instantaneous pickup must be reviewed against permitted inrush and fault-disconnection needs. Ground-fault sensing must match the earthing and neutral arrangement.
| عملکرد | Design input | بررسی کنید |
|---|---|---|
| L | Load and conductor ampacity | Pickup and overload curve |
| S | Downstream protection | Selectivity and withstand |
| I | Inrush and fault level | High-current response |
| G | Earthing and sensing | Pickup, delay and neutral path |
The resulting settings need authorisation, commissioning and change control. Do not disable a function to obtain a cleaner curve without reviewing the resulting protection gap. An LSIG label does not establish a 30 mA residual-current function or a communication interface.
سوالات متداول
What does LSIG stand for?
Long-time, short-time, instantaneous and ground-fault protection. Confirm which functions and setting ranges are present in the exact release.
Does LSIG guarantee selective coordination?
No. Selectivity depends on the actual devices, settings and fault levels. Complete the مطالعه هماهنگي and verify the approved settings.
Is G the same as an RCD’s additional shock protection?
Not automatically. Sensitivity, waveform response and sensing arrangement can differ substantially. Verify the required function separately.
Can settings be changed whenever loads change?
Changes require an approved protection review and updated records. Re-test as required and preserve conductor and equipment protection.
منابع
- IEC 60947-2:2024 — محدوده محصولات قطع کننده مدار.
- IEC 61439-1:2020 – قوانین کلی برای مجموعههای ولتاژ پایین.
- NFPA 70 — توسعه و محدودهٔ کد نصب در ایالات متحده.
برای بررسی پیکربندی پیشنهادی،, تماس با گروه W9 با برنامه بارگذاری، در دسترس است ضریب خطا و الزامات بازار مقصد.





































