Disjuntor de carcasa moldeada WLM7DC-630
DATOS TÉCNICOS
WLM7DC-630 PV DC Molded Case Circuit Breaker Specifications
W9 Group lists WLM7DC-630 as a photovoltaic DC molded case circuit breaker with a 630 A catalog designation and 2P / 3P pole options. Confirm the rated voltage, connection scheme and voltage-specific breaking capacity for the exact offered configuration.
| WLM7DC Moulded Case Circuit Breaker | 630 | ||||||||||||
| Corriente de operación nominal en (A), 40 °C | 400-500-630 | ||||||||||||
| Tensión de aislamiento nominal Ui (V) | 1500 | ||||||||||||
| Tensión de resistencia a la impulsión nominal (kV) | 12 | ||||||||||||
| Tensión operativa nominal Ue(V), CA 50/60Hz | 110/250/500/750/1000/1200/1500 | ||||||||||||
| Código de capacidad de ruptura | – | M | H | ||||||||||
| Número de postes | 2P | – | ■ | ■ | |||||||||
| 3P | – | ■ | ■ | ||||||||||
| DC250V | – | 25 | 50 | ||||||||||
| DC500V | – | 25 | 50 | ||||||||||
|
Calificado como el mejor Desconexión por cortocircuito Capacidad de la instalación de Icu (kA) |
DC750V | – | 15 | 35 | |||||||||
| DC1000V | – | 15(3P30) | 35(3P30) | ||||||||||
| DC1250V | – | – | – | ||||||||||
| DC1500V | – | 10(3P25) | 25 | ||||||||||
|
Servicio de calidad quebrado Capacidad Ics (kA) |
DC250V | – | 25 | 50 | |||||||||
| DC500V | – | 25 | 50 | ||||||||||
| DC750V | – | 15 | 35 | ||||||||||
| DC1000V | – | 15(3P30) | 35 | ||||||||||
| DC1250V | – | – | – | ||||||||||
| DC1500V | – | 10(3P25) | 25 | ||||||||||
| Estándar | IEC/EN 60947-2 | ||||||||||||
| Categoría de utilización | A | ||||||||||||
| Temperatura ambiente | -40℃ ~+70 ℃ | ||||||||||||
| Seguridad de la aislación | ■ | ||||||||||||
| Distancia de arco | 0 | ||||||||||||
|
Vida mecánica (Reciclaje de CO) |
Sin mantenimiento | 20000 | |||||||||||
|
Vida eléctrica (Reciclaje de CO) |
Sin mantenimiento | 2000(DC1500V is :1000times) | |||||||||||
| Unidades de liberación | |||||||||||||
| Protección de la distribución | TM | ■ | |||||||||||
| Instalación y conexión | |||||||||||||
| Corregido | Conexión frontal | ■ | |||||||||||
| Conexión trasera | ■ | ||||||||||||
| Pluggable | Conexión frontal | ■ | |||||||||||
| Conexión trasera | ■ | ||||||||||||
| Desarrollar | Conexión frontal | – | |||||||||||
| Conexión trasera | – | ||||||||||||
| Rápidamente montable en un panel de pared | Conexión frontal | – | |||||||||||
| Dimension | |||||||||||||
|
Dimensiones (mm) W×H×D |
Ancho | 130/182 | |||||||||||
| Altura | 270 | ||||||||||||
| Profundidad | 154.5 | ||||||||||||
| Peso | |||||||||||||
| Peso (kg)/Fijo | 2P | 2 | |||||||||||
| 3P | 8.3 | ||||||||||||
| 4P | – | ||||||||||||
Guía de selección
Selecting a PV DC MCCB by Voltage, Poles and Fault Duty
Specify the AC/DC circuit duty, supply voltage, current, pole arrangement, breaking-capacity code and trip-unit configuration when you request a WLM7DC-630 quotation from W9 Group.
Specify the circuit side
State PV DC maximum voltage and the proposed connection arrangement; confirm the permitted series-pole wiring.
Specify the current and trip unit
Reference WLM7DC-630 and ask for the exact operating current and trip-unit functions. Confirm whether the offered unit is a breaker or switch-disconnector.
Confirm fault duty
Provide prospective fault current and request Icu/Ics at the intended voltage, pole arrangement and capacity code.
Check panel fit
Use the catalog dimensions only for initial planning; request the installation drawing, terminals and clearances for the ordered device.
QUÉ ES W9 GROUP
W9 Group PV DC MCCB Supply and Support
Zhejiang W9 Group Technology Co., Ltd. supplies low-voltage electrical products. For a WLM7DC-630 enquiry, contact W9 Group about configuration and matching product documents.

RECURSOS RELACIONADOS
WLM7DC-630 DC MCCB Datasheet and Connection Drawing Requests
Use W9 Group technical support and the product directory to specify WLM7DC-630. Request the matching datasheet before ordering.
LISTA DE PRODUCTOSExplora los productos de W9 GroupExplore los modelos de W9 Group y solicite las especificaciones del producto seleccionado
DOCUMENTOSCentro de descarga de W9 GroupRequest the current document for your quoted WLM7DC-630 variant
Preguntas frecuentes del comprador
WLM7DC-630 DC MCCB FAQs: Current, Trip Unit and Voltage Checks
Find answers about WLM7DC-630 selection, configuration and ordering.
What does WLM7DC-630 identify?
The catalog identifies the WLM7DC series with a 630 A designation. Confirm the fitted current rating, pole arrangement and complete order code.
Can I apply the highest series voltage to every pole arrangement?
Confirm the rated operational voltage and wiring drawing for the selected pole arrangement. A series voltage list does not establish every voltage/pole combination.
Which protection functions are included?
Request the actual trip-unit configuration and coordination curves. Confirm breaker versus switch-disconnector and any optional accessories in the quotation.
What is needed for a WLM7DC-630 quotation?
Envíe la configuración requerida, la cantidad, el mercado de destino y los requisitos documentales. Solicite a W9 Group que confirme el precio, la cantidad mínima de pedido, las muestras y el plazo de entrega para la configuración seleccionada.
What is this WLM7DC molded case circuit breaker used for?
The source identifies the WLM7DC series for its stated photovoltaic circuit duty, but exact breaker versus switch-disconnector and protection functions depend on configuration. Request the matched datasheet and trip-unit details.
How should I confirm the breaking capacity?
Provide prospective fault current and request Icu/Ics for the intended voltage, pole arrangement and capacity code; do not apply the series voltage list to every configuration.
Solicitud de producto
Request a WLM7DC-630 PV DC MCCB Quotation
Tell W9 Group your AC/DC circuit duty, supply voltage, current, pole arrangement, breaking-capacity code and trip-unit configuration, quantity and destination market so the selected configuration can be identified.