{"id":3669,"date":"2026-02-10T09:00:00","date_gmt":"2026-02-10T01:00:00","guid":{"rendered":"https:\/\/eqsvq3fzct.wpdns.site\/blog\/how-to-install-spd-on-ac-unit-step-by-step-guide\/"},"modified":"2026-02-10T09:00:00","modified_gmt":"2026-02-10T01:00:00","slug":"how-to-install-spd-on-ac-unit-step-by-step-guide","status":"publish","type":"post","link":"https:\/\/w9-group.com\/ru\/blog\/how-to-install-spd-on-ac-unit-step-by-step-guide\/","title":{"rendered":"How to Install SPD on AC Unit Step-by-Step Guide"},"content":{"rendered":"<h2 class=\"wp-block-heading\">What Is an AC Surge Protector?<\/h2>\n<p class=\"wp-block-paragraph\">When many people hear \u201csurge protector,\u201d what comes to mind is the type of multi-socket power strip with a switch, this is the most common misunderstanding and also the most dangerous one.<\/p>\n<p class=\"wp-block-paragraph\">The surge protector used to protect air conditioners, officially known as a<span> <\/span><a href=\"\/ru\/jcst-type-1-2-ac-surge-protection-device-product\/\">Surge Protective Device<\/a><span> <\/span>(SPD), is an industrial-grade protective device specifically installed in electrical systems. It is typically fixed inside the circuit breaker panel or the air conditioner junction box, rather than plugged into wall outlets. Ordinary power strip-type surge protectors cannot withstand the high current generated when an air conditioner starts up; forcing their use may lead to overheating or even fire hazards.<\/p>\n<p class=\"wp-block-paragraph\">Simple distinction:<\/p>\n<table class=\"has-fixed-layout\" style=\"width: 97.267%;\">\n<tbody>\n<tr>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 29.7677%;\">Comparison Item<\/td>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 32.8134%;\">Power Strip Surge Protector<\/td>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 37.4189%;\">AC Dedicated SPD<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 29.7677%;\">Installation Method<\/td>\n<td style=\"width: 32.8134%;\">Plugged into a wall outlet<\/td>\n<td style=\"width: 37.4189%;\">Hardwired into disconnect box or electrical panel<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 29.7677%;\">Typical Application<\/td>\n<td style=\"width: 32.8134%;\">Computers, TVs, and small appliances<\/td>\n<td style=\"width: 37.4189%;\">Air conditioners, heat pumps, and high-power HVAC equipment<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 29.7677%;\">Current Capacity<\/td>\n<td style=\"width: 32.8134%;\">Typically below 15A<\/td>\n<td style=\"width: 37.4189%;\">Can handle 100A+<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 29.7677%;\">Protection Standard<\/td>\n<td style=\"width: 32.8134%;\">No mandatory industrial standard<\/td>\n<td style=\"width: 37.4189%;\">IEC\/EN 61643-11 compliant<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 29.7677%;\">Suitability for AC Units<\/td>\n<td style=\"width: 32.8134%;\"> <span>\u274c\ufe0f <\/span>Not suitable and may pose safety risks<\/td>\n<td style=\"width: 37.4189%;\">\u2705\ufe0f Specifically designed for HVAC systems<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2 class=\"wp-block-heading\">How to Choose the Right Surge Protector for Your AC Unit<\/h2>\n<p class=\"wp-block-paragraph\"><strong>Five key technical parameters<\/strong><\/p>\n<p class=\"wp-block-paragraph\">\u2460 Operating voltage (Uc) \u2013 Must match your circuit.<\/p>\n<p class=\"wp-block-paragraph\">This is the most basic and also the easiest step to make mistakes. The mainstream power supply specifications for American residences are as follows:<\/p>\n<table class=\"has-fixed-layout\" height=\"110\" style=\"width: 97.7575%;\">\n<tbody>\n<tr>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 40.7796%;\">AC System Type<\/td>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 26.53%;\">Typical Power Supply<\/td>\n<td class=\"has-text-align-center\" data-align=\"center\" style=\"width: 29.6551%;\">Required SPD Rated Voltage<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 40.7796%;\">Window AC \/ Small Wall-Mounted Unit<\/td>\n<td style=\"width: 26.53%;\">120V Single-Phase<\/td>\n<td style=\"width: 29.6551%;\">Uc \u2265 130V<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 40.7796%;\">Central AC \/ Split-System Outdoor Unit<\/td>\n<td style=\"width: 26.53%;\">240V Single-Phase (L-L)<\/td>\n<td style=\"width: 29.6551%;\">Uc \u2265 264V<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 40.7796%;\">Commercial Three-Phase HVAC System<\/td>\n<td style=\"width: 26.53%;\">208V \/ 480V Three-Phase<\/td>\n<td style=\"width: 29.6551%;\">Matching Three-Phase SPD<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p class=\"wp-block-paragraph\">\u2461 Peak discharge current (Imax) \u2013 Determines the surge it can withstand<\/p>\n<p class=\"wp-block-paragraph\">Imax is the maximum peak current that an SPD can safely withstand during a single surge. For residential single-phase split air conditioners, it is recommended to choose a<span> <\/span><a href=\"\/ru\/jcspv-photovoltaic-surge-protection-device-1000vdc-solar-surge-product\/\">Type 2 SPD<\/a><span> <\/span>with In (nominal discharge current) \u2265 20kA and install it at the outdoor unit\u2019s circuit breaker box; for commercial three-phase rooftop units or chillers, a Type 1+2 combination product with Iimp \u2265 12.5kA should be selected.<\/p>\n<p class=\"wp-block-paragraph\">Actual purchasing recommendations:<\/p>\n<ul class=\"wp-block-list\">\n<li>Ordinary residential areas, regions with infrequent thunderstorms: Imax \u2265 40kA<\/li>\n<li>Regions with frequent thunderstorms (Florida, Texas, Oklahoma, etc.): Imax \u2265 80kA<\/li>\n<\/ul>\n<p class=\"wp-block-paragraph\">\u2462 Voltage Protection Level (Up \/ Clamping Voltage) \u2013 The lower, the better<\/p>\n<p class=\"wp-block-paragraph\">Up is the maximum residual voltage allowed across both ends of the protector during a surge, directly determining how much \u201cpressure\u201d your air conditioning circuit actually endures.<\/p>\n<p class=\"wp-block-paragraph\">For precision circuit protection, clamping voltage products in the range of 330V\u2013400V should be sought; values below this range indicate better protection performance. An excessively high Up value means that even if the SPD activates, it may still cause damage to the air conditioner control board.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Energy Absorption (Joule Rating)<\/p>\n<p class=\"wp-block-paragraph\">The joule rating represents the total surge energy that the SPD can cumulatively absorb over its lifetime. For air conditioner protection, it is recommended to select products with a joule rating between 1000 and 2000. SPDs specifically designed for outdoor units can have higher joule ratings to provide stronger protection.<\/p>\n<p class=\"wp-block-paragraph\">\u2464 Protection Modes \u2013 L-L \/ L-N \/ L-G Full Coverage<\/p>\n<p class=\"wp-block-paragraph\">Surges can enter the circuit through different paths, and a complete SPD should cover three protection modes:<\/p>\n<ul class=\"wp-block-list\">\n<li>L-L (Line to Line): Prevents voltage differential surges between two live wires.<\/li>\n<li>L-N (Line to Neutral): Prevents surges between the live wire and the neutral wire.<\/li>\n<li>L-G (Line to Ground): Prevents potential difference surges between the live wire and the ground wire.<\/li>\n<\/ul>\n<h2 class=\"wp-block-heading\">Step-by-Step Surge Protector Installation Guide<\/h2>\n<p itemscope=\"1\" itemtype=\"http:\/\/schema.org\/ImageObject\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/ecdn6.globalso.com\/upload\/p\/1205\/image_other\/2025-12\/jcst-3p-n-right-side.jpg\" alt=\"JCST 3P+N \u53f3\u4fa7\u9762.jpg\" width=\"309\" height=\"309\" style=\"display: block; margin-left: auto; margin-right: auto;\" itemprop=\"image\"><\/p>\n<h3 class=\"wp-block-heading\">Step 1: Power Shutdown &amp; Verification<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Locate the dedicated circuit breaker for the air conditioner in the main distribution box.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Switch the circuit breaker to OFF position. Use both hands to ensure it is securely set to OFF and will not spring back.<\/p>\n<p class=\"wp-block-paragraph\">\u2462 Go to the outdoor unit disconnect box and perform secondary power disconnection. The outdoor unit disconnect box (Disconnect Box) is usually installed on a wall within 1 meter of the outdoor unit\u2019s side. Open its cover, completely pull out the internal pullout fuse block, or switch it off inside the box.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Measure voltage across three pairs of endpoints using a multimeter; confirm all readings are 0V: Zero voltage verification must not rely solely on switch positions-use a calibrated multimeter or non-contact voltage tester to measure L-N (live-neutral), L-PE (live-ground), N-PE (neutral-ground) separately, ensuring all readings are 0V.<\/p>\n<p class=\"wp-block-paragraph\">\u2464 Wait at least 5 minutes: Allow residual charge in capacitors within circuits to naturally dissipate before touching any wires afterward.<\/p>\n<p class=\"wp-block-paragraph\">\u2465 Attach an LOTO warning label: Place sticky notes or hang warning signs on breakers in the main distribution box stating \u201cOperation in progress, do not turn ON\u201d-to prevent accidental operation by others during your work period at home.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 2: Open Disconnect Box &amp; Inspect<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Use a Phillips or flathead screwdriver to loosen the screws securing the breaker box, remove the panel cover, and place it on a clean, dry surface to avoid obstructing the work area.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Take a photo of the current wiring setup (highly recommended). This photo will serve as your most valuable \u201creference for restoration\u201d in case of incorrect wiring later.<\/p>\n<p class=\"wp-block-paragraph\">\u2462 Visually inspect the internal wiring conditions:<\/p>\n<p class=\"wp-block-paragraph\">Focus on checking these four points:<\/p>\n<ul class=\"wp-block-list\">\n<li>Whether the wire insulation is intact, with no cracks, scorching, or discoloration.<\/li>\n<li>Whether there are signs of corrosion, oxidation, or loosening at terminal connections.<\/li>\n<li>Whether there are insect nests or water stains inside (commonly found in outdoor-installed breaker boxes).<\/li>\n<li>Whether existing wire colors comply with standards (Black\/Red = Live Wire; White = Neutral Wire; Green\/Bare Copper = Ground Wire).<\/li>\n<\/ul>\n<p class=\"wp-block-paragraph\">If damaged wires, scorch marks, or severely corroded terminals are found, immediately stop operations and contact a licensed electrician before proceeding with SPD installation.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Confirm whether there is enough space in the junction box to install the SPD.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 3: Mount the SPD<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Select the installation hole location<\/p>\n<p class=\"wp-block-paragraph\">Junction boxes usually have \u201cknockout holes\u201d on the sides or bottom-these are thin-walled, circular pre-drilled holes specifically designed for installing accessories. They can be opened by lightly tapping with a screwdriver and hammer, typically with diameters of 1\/2 inch or 3\/4 inch.<\/p>\n<p class=\"wp-block-paragraph\">If mounting the SPD on an exterior wall, mark the installation hole position with a pencil to ensure alignment with screw holes on the wall or junction box.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Secure the SPD housing<\/p>\n<p class=\"wp-block-paragraph\">Use matching screws to secure the SPD in place. When tightening screws, pay attention:<\/p>\n<ul class=\"wp-block-list\">\n<li>Screws should be tightened firmly but not excessively-over-tightening may deform the plastic housing and affect waterproof sealing performance.<\/li>\n<li>If installed on an outdoor wall, use accompanying rubber waterproof gaskets to ensure sealing around installation holes.<\/li>\n<\/ul>\n<p class=\"wp-block-paragraph\">\u2462 Confirm that after securing, the SPD does not wobble and its terminals are positioned for easy operation.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 4: Wiring Operation<\/h3>\n<p class=\"wp-block-paragraph\">Connect the live wire (L) to the L terminal, the neutral wire (N) to the N terminal, and the ground wire (PE) to the PE terminal. Then use a screwdriver to tighten each terminal screw-loose terminal connections are one of the main causes of overheating or even fire.<\/p>\n<p class=\"wp-block-paragraph\">Step-by-step instructions for each wire:<\/p>\n<ol start=\"1\" class=\"wp-block-list\">\n<li>Live Wire (L Terminal): Insert the black (or red) wire into the L terminal hole and tighten the terminal screw clockwise with a screwdriver. If using a torque screwdriver, refer to the torque value specified in the product manual (usually 2.0\u20133.5 Nm).<\/li>\n<li>Neutral Wire (N Terminal): Insert the white wire into the N terminal hole and similarly tighten its screw.<\/li>\n<li>Ground Wire (PE Terminal): Insert either a green or bare copper ground wire into the PE terminal hole and tighten its screw.<\/li>\n<\/ol>\n<p class=\"wp-block-paragraph\">After completing all connections, gently pull on each wire by hand to ensure none can be easily pulled out. If any wires are loose, retighten their respective screws.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 5: Grounding<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Confirm that the grounding wire specifications meet requirements. The grounding terminal (PE) should use copper wires with a cross-sectional area of no less than 4mm\u00b2 (approximately AWG 12 in American standards) to connect to the local Grounding Bus Bar, ensuring sufficient conduction cross-section for surge currents.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Keep the grounding path short and straight. The grounding wire from the SPD\u2019s PE terminal to the Grounding Bus Bar or circuit box\u2019s grounding screw should be as short and straight as possible, avoiding bends-the shorter and straighter the grounding wire, the lower its impedance, resulting in faster SPD response speed and better protection performance.<\/p>\n<p class=\"wp-block-paragraph\">\u2462 Check if the grounding system is reliable. Ensure that connections between the ground wire and ground rod or copper cold water pipe are secure and reliable. Outdoor ground points should not use mechanical clamps (Acorn Clamp) prone to loosening over time; crimping or welding methods are recommended for fixation.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Verify continuity of grounding using a multimeter. Set a multimeter to resistance mode (\u03a9), connecting one end to the PE terminal and another end to a known reliable earth point (e.g., copper cold water pipe). The resistance value should be less than 1\u03a9. If it is too high, this indicates breaks or poor contact in the grounding line.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 6: Tidy Wiring &amp; Close Panel<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Check that all wires maintain a safe distance from moving parts. Ensure the wires do not come into contact with the movable components of the circuit breaker box switch and are not pinched when the cover is closed.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Secure wiring using cable ties or clamps. Bundle excess wires neatly with plastic cable ties and fix them to an appropriate position on the inner or outer wall of the circuit breaker box to prevent dangling, reducing the risk of terminal loosening caused by long-term vibration.<\/p>\n<p class=\"wp-block-paragraph\">\u2462 Insulate exposed parts of wires. If there are any exposed copper areas at wire joints or stripped sections (except for those already inserted into terminals), wrap them with electrical tape for insulation to ensure they do not come into contact with other metal components.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Attach installation date labels on SPD housing or wires. Record the installation date to facilitate determining SPD\u2019s service life during future maintenance.<\/p>\n<p class=\"wp-block-paragraph\">\u2464 Reattach and tighten screws on the circuit breaker box panel cover. Ensure proper sealing of the panel cover, especially for outdoor installations, as any gaps could allow rainwater or insects to enter.<\/p>\n<div aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n<h3 class=\"wp-block-heading\">Step 7: Power Restore &amp; Verification<\/h3>\n<p class=\"wp-block-paragraph\">\u2460 Remove all tools and ensure the construction area is clean. Store away tools such as multimeters, screwdrivers, wire strippers, etc., and confirm that no metal tools are left inside the circuit breaker box.<\/p>\n<p class=\"wp-block-paragraph\">\u2461 Restore power to the outdoor unit\u2019s circuit breaker box first. Reinsert the removed fuse components or switch the breaker inside to ON.<\/p>\n<p class=\"wp-block-paragraph\">\u2462 Return to the main distribution panel and restore the dedicated air conditioner circuit breaker. Remove LOTO warning labels and switch the breaker to ON.<\/p>\n<p class=\"wp-block-paragraph\">\u2463 Immediately observe SPD status indicator lights. Check the status window on SPD housing: green indicates normal operation with protection activated; if unlit, red, or showing abnormal colors, it means equipment damage or installation issues-power off immediately for inspection.<\/p>\n<p class=\"wp-block-paragraph\">\u2464 Start up the air conditioner and confirm normal operation. Lower air conditioning temperature by 2\u00b0C and observe whether the outdoor unit starts normally (compressor running, fan spinning). Also verify that SPD indicator light remains green during startup; some inferior products may flicker or turn off under startup current impact-a sign of product quality issues.<\/p>\n<h3 class=\"wp-block-heading\">W9 GROUP AC SPD Features<\/h3>\n<p>JCS<span>T<\/span> Surge protection devices are designed to absorb and dissipate the excess electrical energy caused by power surges, ensuring that the equipment connected to the system is not damaged. JCS<span>T<\/span> SPDs can help prevent costly equipment downtime, repairs, and replacements.<\/p>\n<p>JCS<span>T<\/span> surge arrestors are designed to absorb and dissipate the excess electrical energy caused by power surges, ensuring that the equipment connected to the system is not damaged. This SPDs can help prevent costly equipment downtime, repairs, and replacements. The devices are also designed to be easy to install and maintain.<\/p>\n<p>JCS<span>T<\/span> Spds is characterized by its capacity to safely discharge current with 8\/20 \u00b5s wave form. T2 and T2+3 SPDs are available in specific multi-pole versions for all distribution systems.<\/p>\n<p>Our JCS<span>T<\/span> surge protection device is built with the latest technology and a sleek, modern design that will blend seamlessly with any electrical system. It is DIN-rail mountable, making it easy to install and use in a variety of settings.<\/p>\n<p>One of the most critical features of our surge protection device is its nominal discharge current In 30kA (8\/20 \u00b5s) per path. This means that it can withstand high levels of electrical surges without causing any harm to your equipment. Furthermore, its maximum discharge current Imax 60kA (8\/20 \u00b5s) makes it a powerful tool in preventing damage caused by surges.<\/p>\n<p>Our JCS<span>T<\/span> Surge protection device is ergonomically designed to ensure maximum protection for all of your electronics. It is crafted from high-quality materials and carefully tested to ensure that it can withstand any power surge.<\/p>\n<p><span style=\"font-size: 18px;\"><strong>W9 GROUP Brand Highlights and Introduction<\/strong><\/span><\/p>\n<p><span style=\"font-size: 18px;\"><strong itemscope=\"1\" itemtype=\"http:\/\/schema.org\/ImageObject\"><img decoding=\"async\" src=\"https:\/\/ecdn6.globalso.com\/upload\/p\/1205\/image_other\/2026-06\/w9-logo.png\" alt=\"W9 logo .png\" style=\"display: block; margin-left: auto; margin-right: auto;\" itemprop=\"image\"><\/strong><\/span><\/p>\n<p><span style=\"font-size: 18px;\">\u201cW9\u201dwas Founded in 2024, and is headquartered in Yueqing Wenzhou, the city of electrical appliances in China. It is a modern manufacturing company which includes trading and manufacturing, researching and development design&#8230; The total factory area is 37000 square meters. The total annual sales of W9 group are 500 million RMB. We are committed to building a group enterprise, strictly controlling the quality, and providing customers with more convenient and cost-effective services. As a major export brand in 2020, W9 Group&#8217;s main partners are domestic mid to high end brand strategic partners. Its product marketing is spread throughout the country and it has exported to more than 20 countries and regions around the world, notably Iran, the Middle East, Russia, Australia, the United Kingdom, etc.W9 has taken the lead in passing ISO9001, ISO140001, OHSAS18001 and other system certifications in the industry. Its products comply with IEC international standards and hold over a hundred product patents, it comprehensively upgrades low-voltage electrical product technology, leads the low-voltage electrical industry in digitalization and intelligence, and provide customers with high-quality somart,systematic products and service,as well as solutions tailored to their specific needs<\/span><\/p>","protected":false},"excerpt":{"rendered":"<p>Protect your air conditioning system from lightning strikes and power fluctuations that can cause silent damage to compressors and control boards<\/p>","protected":false},"author":1,"featured_media":3822,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-3669","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"_links":{"self":[{"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/posts\/3669","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/comments?post=3669"}],"version-history":[{"count":0,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/posts\/3669\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/media\/3822"}],"wp:attachment":[{"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/media?parent=3669"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/categories?post=3669"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/w9-group.com\/ru\/wp-json\/wp\/v2\/tags?post=3669"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}